| 2012-12-14 14:30:06 | 629 CLEAR LAKE AVENUE | | | PERMIT #12120450 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAIL: FBC SECTION 105.3.1.2: ENGINEERED FIRE ALARM | | | DRAWINGS SHALL BE SIGNED AND SEALED BY A REGISTERED | | | PROFESSIONAL ENGINEER (NOT AN ARCHITECT) PER FLORIDA | | | STATUTE 471. | | | | | | PROVISO: A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | PROVISO: FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED | | | AND IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|