| Plan Review Notes For Permit 12120434 |
| Permit Number |
12120434 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-31 16:14:10 | 12120434 | | | 1921 SOUTH DIXIE HIGHWAY | | | COMMERCIAL RENOVATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENT. | | | | | | VERIFY THE NEW AND EXISTING SERVICE EQUIPMENT IS | | | SUFFICIENT TO HANDLE THE AVAILABLE FAULT CURRENT. NEC | | | 110.9 | | | | | | PROVIDE DEDICATED 20 AMPERE BRANCH CIRCUIT (S) FOR | | | SIGNAGE. NEC 600.5 | | | | | | GFCI PROTECTION IS REQUIRED FOR WATER COOLERS. NEC | | | 422.52 | | | | | | THE GENERATOR REQUIRES A SEPARATE PERMIT WITH PLANS AND | | | SPECIFICATIONS. PLEASE INCLUDE CONDUIT SUPPORT AND | | | FLASHING DETAIL FOR ALL CONDUIT AND EQUIPMENT. INCLUDE | | | ENGINEERING FOR THE SUPPORT AND ANCHORAGE OF THE | | | GENERATOR. FBC 105.1 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|