| 2012-12-28 16:25:27 | BUILDING PLAN REVIEW |
| | PERMIT: 12120418 |
| | ADD:1155 BELVEDERE RD |
| | CONT: TBD |
| | TEL: (305) 710-1118 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DEC. 28/2012 |
| | ACTION: DENIED |
| | 1) PLEASE BREAK UP THE PROJECT INTO A PERMIT FOR EACH |
| | OF THE BUILDINGS WHERE WORK IS GOING TO BE PREFORMED. |
| | THIS PERMIT WILL BE FOR THE EXISTING BUILDING BUILT |
| | UNDER THE 1201 BELVEDERE ADDRESS IN 1963. PULL THE |
| | VALUE OUT OF THIS PERMIT AND APPLY IT APPROPRIATELY TO |
| | THE OTHER BUILDINGS LABELED A, B & C. |
| | |
| | 2) SHEET A0.01 INDICATES A LEVEL II ALTERATION |
| | OCCURING, PLEASE BREAK OUT AND IDENTIFY EACH BUILDING |
| | BY BUILDING TYPE AND ALTERATION LEVEL FOR EACH BUILDING |
| | SEPERATELY. THE 1201 BELVEDERE BUILDING WILL BE |
| | CONSIDERED A LEVEL III ALTERATION AS WELL AS A VERTICAL |
| | ADDITION. PLEASE REVIEW THE REQUIREMENTS FOUND IN 2010 |
| | EXST BLDG CODE 807.2- 807.4.1. |
| | |
| | 3) 2010 FLORIDA EXIST BLDG CODE 1001.2 CREATION OR |
| | EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT |
| | CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE ADDITION IS BEING MADE WITH |
| | REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE |
| | SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL, |
| | PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | THE PROPOSED PENTHOUSE OR ARCHITECTURAL EMBELLISHMENT |
| | ON THE EXISTING BUILDING ADDRESSED AT 1201 BELVEDERE RD |
| | WAS BUILT IN 1963 UNDER THE CODE IT WAS BUILT A BLDG |
| | TYPE VB, THE CURRENT 2010 FBC CODE ( BLDG TYPE IIIB) IN |
| | 1963, WHICH ALLOWED WOOD ROOF FRAMING AND SHEATHING, |
| | THE PROPOSED VERTICAL ADDITION IS INDICATED TO BE A |
| | TYPE IB SEE SHEET A0.01. UNDER THE 2010 FBC 603.1.1 |
| | ONLY FIRE RETARDANT TREATED WOOD CAN BE USED IN THE |
| | ROOF SYSTEM THE PLANS INDICATE THE EXISTING ROOF |
| | FRAMING TO REMAIN CREATING A NONCONFORMITY. |
| | |
| | 4) SHEET A1.01 INDICATES WALL SECTIONS FOUND ON SHEET |
| | A3.01 AND DETAILS FOUND ON A3.02 THESE PLANS DO NOT |
| | PROVIDE ANY MAIN WIND FORCE RESISTING SYSTEM DETAILS, |
| | THESE PLANS AS DRAWN ARE CONCEPTUAL, NOT PLANS THAT CAN |
| | BE USED FOR CONSTRUCTION DOCUMENTS, |
| | EXST BLDG CODE 807.2 NEW STRUCTURAL ELEMENTS. |
| | NEW STRUCTURAL ELEMENTS SHALL COMPLY WITH SECTION |
| | 707.2. |
| | |
| | EXST BLDG CODE 807.3 EXISTING STRUCTURAL ELEMENTS |
| | CARRYING GRAVITY LOADS. |
| | EXISTING STRUCTURAL ELEMENTS CARRYING GRAVITY LOADS |
| | SHALL COMPLY WITH SECTION 707.4. |
| | |
| | 5) MISSING WIND DESIGN CRITERIA: |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 6) |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, DENSE GLASS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 7) SHEET A1.01 RESTROOM ENLARGED DETAIL, THE DOOR |
| | SWINGS IN OVER THE REQUIRED CLEAR FLOOR SPACE FOR BOTH |
| | THE LAV AND WATER CLOSET. 2010 ACCESSIBILITY CODE |
| | 604.3.2 & 606.2. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |