| Plan Review Notes For Permit 12120412 |
| Permit Number |
12120412 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-26 16:58:07 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. TWO SETS OF PLANS REQUIRED FOR PERMIT ISSUANCE, FBC | | | 107.1. | | | | | | 2. SITE PLAN REQUIRED, FBC 107.2.5. SITE PLAN SHOULD | | | SHOW DISTANCE OF PROPOSED IMPROVEMENT FROM LOT LINES. | | | | | | 3. REVISE PLAN TO INCLUDE DESIGN CRITERIA, FBC R | | | 301.1.2.1.1. WIND SPEED AND EXPOSURE CLASSIFICATION | | | SHOULD BE INCLUDED. | | | | | | 4. ELEVATION OF PROPOSED PORCH RELATIVE TO FINISHED | | | FLOOR OF HOUSE IS NOT CLEAR, FBC R 311.2, 311.3.2. | | | REVISE PLAN TO INCLUDE REQUIRED EGRESS DOORS IF USING | | | R311.3.2. | | | | | | 5. THERE IS AN EXISTING VIOLATION AND EXPIRED PERMITS | | | ON THIS PROPERTY FOR AN ADDITION. PLEASE ADDRESS. | | | |
|