| Plan Review Notes For Permit 12120394 |
| Permit Number |
12120394 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-03-04 15:56:33 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS: A) ITEM #7 EXCEEDS THE | | | 20% OF GLASS AREA. FORM 402-2010 CAN'T BE USED. SEE | | | GENERAL INSTRUCTIONS #1 ON TOP OF FORM. B) ITEM #9A2 | | | AND ARCHITECTURAL PLANS NEED TO BE COORDINATED AND | | | MATCH. C) PROVIDE NAME OF BUILDER ON TOP OF FORM. | | | 2- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF | | | 2010 FBC-RESIDENTIAL. | | | ***NOTE: THIS MAY BE SUBMITTED LATER, BUT IT WILL BE ON | | | CONTRACTOR'S OWN RISK IF FOOTINGS NEED TO BE | | | RE-DESIGNED. | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) CONCRETE TILE TO BE USED ON 2:12 PITCH. NOA | | | 12-0529.12 DOESN'T ALLOW 2:12 PITCH. | | | B) CONCRETE TILE ADHESIVE AS LISTED ON CONCRETE TILE | | | PRODUCT APPROVAL. | | | C) SIMPSON CONNECTOR HGAM10. OR, APPLY FOR LOCAL | | | PRODUCT APPROVAL. | | | D) DOORS WITH SIDELITES AS SHOWN ON PLANS. NEED DOORS | | | THAT MEET THE CALCULATED DESIGN PRESSURES. | | | E) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8" | | | PRECAST LINTELS. | | | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS | | | TO FBC. | | | |
|