| Plan Review Notes For Permit 12120394 |
| Permit Number |
12120394 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-19 09:04:13 | ** CORRECTIONS NEEDED FOR MECHANICAL PLAN REVIEW *** | | | | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2010 | | | FBC/ENERGY 401.2. | | | | | | 2) SUBMIT COOLING LOAD CAL'S. PER 2010 FBC/ENERGY | | | 403.6.1. | | | | | | 3) SHOW ON MECHANICAL PLAN THE LOCATION OF THE | | | CONDENSER UNIT. ALSO SHOW AN A/C EQUIPMENT LISTING WITH | | | MAKE, SIZE, SEER, BTU'S TOTAL & SENSIBLE, ETC. PER 2010 | | | CITY OF WPB AMEND. 107.3.5.3 (10). | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|