Plan Review Notes
Plan Review Notes For Permit 12120370
Permit Number 12120370
Review Stop P
Sequence Number 1
Notes
Date Text
2012-12-19 09:20:59 
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. THE WATER SOFTENER BACK WASH DRAIN IS REQUIRED TO
 DRAIN TO THE SANITARY.
 SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A)
 GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
  
 2. THE WELL WATER CAN NOT INTERCONNECT WITH THE CITY
 WATER FOR THE IRRIGATION SYSTEM. THE COOLING TOWERS
 WILL BE OK IF THERE IS AN AIR GAP.
 SEC. 90-33. - REGULATION OF CROSS CONNECTION.
 AS USED IN THIS SECTION, THE TERM "CROSS CONNECTION"
 MEANS ANY PHYSICAL ARRANGEMENT WHEREBY THE CITY'S
 PUBLIC WATER SYSTEM IS CONNECTED, DIRECTLY OR
 INDIRECTLY, WITH ANY OTHER WATER SUPPLY SYSTEM...
  
 NOTE** A WELL PERMIT FROM PALM BEACH COUNTY HEALTH
 DEPT. IS REQUIRED FOR THE WELL. A COPY OF THE PERMIT IS
 REQUIRED ONSITE AT TIME OF INSPECTION.
 HTTP://WWW.PBCHD.COM/ENV/ENVIRONMENTAL.HTML
  