| Date |
Text |
| 2013-01-07 11:14:02 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SCREEN ROOF PLAN IS TOO SMALL TO READ AND SCAN, | | | WALLS DO NOT SHOW DIMENSIONS OF ALUMINUM MEMBERS AND | | | SPANS. PROVIDE A PLAN, 1/8" SCALE MINIMUM, FBC 107. | | | | | | 2. PLAN REQUIRES A MINIMUM 8X8 FOOTER. NO FOOTER | | | PROPOSED ON THE PLAN, SO HOW HAVE YOU DETERMINED THAT | | | AN 8X8 FOOTER WITH 1 #5 IS EXISTING? FBC 301. | | | | | | 3. IT IS NOT CLEAR WHERE THE SCREEN ROOF WILL BE | | | INSTALLED. PLAN SHOWS A HATCHED 12X12 AREA, NON | | | CONSISTENT WITH THE ROOF PLAN. PROVIDE A SITE PLAN | | | WHICH CLEARLY SHOWS EXISTING AND PROPOSED. A SURVEY | | | WOULD BE HELPFUL. FBC 106. | | | | | | |
|