Plan Review Notes
Plan Review Notes For Permit 12120366
Permit Number 12120366
Review Stop B
Sequence Number 1
Notes
Date Text
2013-01-07 11:14:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SCREEN ROOF PLAN IS TOO SMALL TO READ AND SCAN,
 WALLS DO NOT SHOW DIMENSIONS OF ALUMINUM MEMBERS AND
 SPANS. PROVIDE A PLAN, 1/8" SCALE MINIMUM, FBC 107.
  
 2. PLAN REQUIRES A MINIMUM 8X8 FOOTER. NO FOOTER
 PROPOSED ON THE PLAN, SO HOW HAVE YOU DETERMINED THAT
 AN 8X8 FOOTER WITH 1 #5 IS EXISTING? FBC 301.
  
 3. IT IS NOT CLEAR WHERE THE SCREEN ROOF WILL BE
 INSTALLED. PLAN SHOWS A HATCHED 12X12 AREA, NON
 CONSISTENT WITH THE ROOF PLAN. PROVIDE A SITE PLAN
 WHICH CLEARLY SHOWS EXISTING AND PROPOSED. A SURVEY
 WOULD BE HELPFUL. FBC 106.
  
  