| Notes |
| Date |
Text |
| 2012-12-11 10:22:56 | 1475 CENTREPARK BLVD - #130 | | | PERMIT #12120268 | | | MASTER #12100851 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FOUR SPRINKLERS ARE LOCATED MORE THAN 9'-0" (MEASURED | | | PERPENDICULAR) IN "SMALL ROOMS" #128 AND #129. | | | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | | UPWARD MOVEMENT. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|