| 2012-12-17 12:56:52 | *** MECHANICAL CORRECTIONS NEEDED *** |
| | |
| | 1) PLAN M2 SHOWS DETAIL FOR ROOF MOUNTED CONDENSER |
| | UNIT. PER 2010 FBC 1509.7 MECHANICAL UNITS. ROOF |
| | MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | PLEASE COMPLY WITH TABLE 1509.7. |
| | |
| | 2) PLAN M1 NOTE #6 STATES CONDENSATE FROM AHU-1 TO |
| | DRAIN INTO MOP SINK, THIS IS PROHIBITED PER. CODE OF |
| | ORDINANCES CH. 90 ARTICLE III SEC 90-126. PROHIBITIONS |
| | AND LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS |
| | SHALL NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN |
| | ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE |
| | PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY |
| | WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR |
| | INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF. |
| | NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED |
| | SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE |
| | FOLLOWING: |
| | (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN |
| | WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING |
| | POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| | UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| | CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| | IN WRITING. |
| | |
| | MECHANICAL PLAN REVIEW BY: |
| | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |