| Plan Review Notes For Permit 12120229 |
| Permit Number |
12120229 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-14 08:50:01 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 09-0224.01 SUBMITTED. NEED THE NAIL ENHANCING | | | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY | | | SEC. 1609.4.3 OF 2010 FBC. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATIONS WAS UPDATED AS REQUIRED BY SEC. 109.3 | | | OF CITY AMENDMENTS TO FBC. OWE THE PERMIT FEE BALANCE | | | OF S$35.68. PAY THIS AT TIME OF PERMIT PICK UP. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|