2012-12-20 09:37:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1.) DESIGN CRITERIA STATED BUT NOT CLEAR WHETHER THIS
 IS WITH AWNING COVER IN PLACE, SEE FBC3105.4.
  
 2.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO
 SHOW COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 3.) IF DESIGNED FOR FABRIC REMOVAL WHEN WINDS EXCEED
 75MPH, PER BUILDING OFFICIAL, WE ARE TO PUT ON THE
 PERMIT FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY
 THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE THEIR
 RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED PRIOR
 TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH
 OR GREATER. THE LETTER/FORM MUST BE SIGNED BY THE OWNER
 BUT IT NEED NOT BE NOTARIZED.
  
 4.) FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 5.) FBC3105.1.1, FBC 1003.3.1, PROVIDE HEIGHT OF LOWEST
 PORTION OF AWNING AS WELL AS A SITE PLAN TO SHOW
 PROPOSED LOCATIONS.
  
 6.) NO INFORMATION PROVIDED REGARDING AWNING COVER,
 REVISE PLAN TO INCLUDE, FBC 3501, 106.
  
 7.) CITY PLACE APPROVAL STAMP REQUIRED ON PLANS, SEE
 ZONING COMMENTS.
  
  