| Plan Review Notes For Permit 12120222 |
| Permit Number |
12120222 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-17 15:26:36 | RESIDENTIAL (R3) FOUNDATION FOR MOVED BUILDING SECOND | | | REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE DRAINAGE ARROWS SHOWN ON SURVEY. WATER NEEDS | | | TO BE DIVERTED TO A STORM SEWER OR OTHER APPROVED POINT | | | OF COLLECTION AND AWAY FROM FOUNDATION WALLS. SEE SEC. | | | R401.3 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | UNDER-FLOOR SPACE VENTILATION AS REQUIRED BY SEC. R408 | | | OF 2010 FBC-RESIDENTIAL. ENGINEER OF RECORD TO SPECIFY | | | ON PLANS SPECIFIC SIZES, LOCATION AND ACCESS SHOWING | | | COMPLIANCE WITH THIS SECTION. INFORMATION NO SUBMITTED. | | | | | | 3- UNDER-FLOOR SPACE FINISHED GRADE TO COMPLY WITH SEC. | | | R408.6. ENGINEER OF RECORD TO PROVIDE COMPLETE | | | SPECIFICATIONS AND DETAILS SHOWING COMPLIANCE. | | | COORDINATE WITH ITEM #1 ABOVE. | | | | | | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE PROTECTION OF WOOD AND WOOD BASED | | | PRODUCTS AGAINST DECAY AS REQUIRED BY SEC. R317 OF 2010 | | | FBC-RESIDENTIAL. ENGINEER OF RECORD TO PROVIDE THIS | | | INFORMATION ON PLANS TO SHOW COMPLIANCE. THE FLOOR OF | | | THE HOUSE TO BE MOVED IS WOOD. SPECIFY HOW PROTECTING | | | THE WOOD FROM THE EXPOSED FINISHED GRADE. SEE SEC. | | | R317. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|