2013-01-17 15:26:36RESIDENTIAL (R3) FOUNDATION FOR MOVED BUILDING SECOND
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE DRAINAGE ARROWS SHOWN ON SURVEY. WATER NEEDS
 TO BE DIVERTED TO A STORM SEWER OR OTHER APPROVED POINT
 OF COLLECTION AND AWAY FROM FOUNDATION WALLS. SEE SEC.
 R401.3 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 UNDER-FLOOR SPACE VENTILATION AS REQUIRED BY SEC. R408
 OF 2010 FBC-RESIDENTIAL. ENGINEER OF RECORD TO SPECIFY
 ON PLANS SPECIFIC SIZES, LOCATION AND ACCESS SHOWING
 COMPLIANCE WITH THIS SECTION. INFORMATION NO SUBMITTED.
  
 3- UNDER-FLOOR SPACE FINISHED GRADE TO COMPLY WITH SEC.
 R408.6. ENGINEER OF RECORD TO PROVIDE COMPLETE
 SPECIFICATIONS AND DETAILS SHOWING COMPLIANCE.
 COORDINATE WITH ITEM #1 ABOVE.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE PROTECTION OF WOOD AND WOOD BASED
 PRODUCTS AGAINST DECAY AS REQUIRED BY SEC. R317 OF 2010
 FBC-RESIDENTIAL. ENGINEER OF RECORD TO PROVIDE THIS
 INFORMATION ON PLANS TO SHOW COMPLIANCE. THE FLOOR OF
 THE HOUSE TO BE MOVED IS WOOD. SPECIFY HOW PROTECTING
 THE WOOD FROM THE EXPOSED FINISHED GRADE. SEE SEC.
 R317.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL