Plan Review Notes
Plan Review Notes For Permit 12120213
Permit Number 12120213
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-17 09:14:07*** PROVISO ***
 1) MASTER SUITE RETURN AIR DUCT MAY NEED TO BE
 ENLARGED. SEE 2010 FBC/RES. M1602.4 BALANCED RETURN
 AIR.
 PROVISIONS SHALL BE MADE IN BOTH RESIDENTIAL AND
 COMMERCIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND
 PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR.
 PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) OR LESS. (3) HABITABLE ROOMS ONLY
 SHALL BE REQUIRED TO MEET THESE REQUIREMENTS FOR PROPER
 BALANCED RETURN AIR EXCLUDING BATHROOMS, CLOSETS,
 STORAGE ROOMS AND LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE INCLUDED.
  