| Plan Review Notes For Permit 12120213 |
| Permit Number |
12120213 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-17 09:14:07 | *** PROVISO *** | | | 1) MASTER SUITE RETURN AIR DUCT MAY NEED TO BE | | | ENLARGED. SEE 2010 FBC/RES. M1602.4 BALANCED RETURN | | | AIR. | | | PROVISIONS SHALL BE MADE IN BOTH RESIDENTIAL AND | | | COMMERCIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND | | | PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. | | | PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | | RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 | | | INCH WC (2.5 PASCALS) OR LESS. (3) HABITABLE ROOMS ONLY | | | SHALL BE REQUIRED TO MEET THESE REQUIREMENTS FOR PROPER | | | BALANCED RETURN AIR EXCLUDING BATHROOMS, CLOSETS, | | | STORAGE ROOMS AND LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE INCLUDED. | | | |
|