2013-05-18 19:21:18424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 THE FIRE-RATED HAZARD SEPARATION APPLIES TO THE WALL
 AND DOORS BETWEEN WAREHOUSE #118 (STORAGE) AND
 SHOWROOMS #113, #114 & #117 (MERCANTILE/BUSINESS). THE
 OTHER WALLS AND DOORS DO NOT NEED TO BE FIRE RATED!
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE/BUSINESS) OF THE BUILDING, SHALL BE
 SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER. DOORS SHALL BE SELF CLOSING,
 POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730