Plan Review Notes
Plan Review Notes For Permit 12120211
Permit Number 12120211
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-04-03 11:09:28424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - PROVIDE DRAWING NOTE: DESIGN SHALL
 CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 REPEAT COMMENT - PROVIDE DRAWING NOTE: ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 RESPONSE COMMENT: THE LIFE SAFETY CODE REQUIRES A
 1-HOUR HAZARD SEPARATION WHICH IS DIFFERENT THAN AN
 OCCUPANCY SEPARATION (WHICH WOULD BE A 2-HOUR FIRE
 BARRIER).
 ORIGINAL COMMENT: ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE/BUSINESS) OF THE BUILDING, SHALL BE
 SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER. DOORS SHALL BE SELF CLOSING,
 POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 SHEET A1.1: THE RESUBMITTED PLANS HAVE INCORRECTLY
 CHANGED THE FURNITURE SHOWROOM FROM MERCANTILE
 OCCUPANCY TO STORAGE OCCUPANCY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved