| Date |
Text |
| 2013-04-03 11:09:28 | 424 PALM STREET |
| | PERMIT #12120211 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REPEAT COMMENT - PROVIDE DRAWING NOTE: DESIGN SHALL |
| | CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH |
| | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | REPEAT COMMENT - PROVIDE DRAWING NOTE: ALL CONSTRUCTION |
| | AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | RESPONSE COMMENT: THE LIFE SAFETY CODE REQUIRES A |
| | 1-HOUR HAZARD SEPARATION WHICH IS DIFFERENT THAN AN |
| | OCCUPANCY SEPARATION (WHICH WOULD BE A 2-HOUR FIRE |
| | BARRIER). |
| | ORIGINAL COMMENT: ANY AREA (STORAGE) HAVING A DEGREE OF |
| | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY |
| | (MERCANTILE/BUSINESS) OF THE BUILDING, SHALL BE |
| | SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR |
| | FIRE-RATED BARRIER. DOORS SHALL BE SELF CLOSING, |
| | POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST |
| | 45-MINUTES PER SECTION 8.7 OF NFPA 101. |
| | |
| | SHEET A1.1: THE RESUBMITTED PLANS HAVE INCORRECTLY |
| | CHANGED THE FURNITURE SHOWROOM FROM MERCANTILE |
| | OCCUPANCY TO STORAGE OCCUPANCY. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |