| Date |
Text |
| 2013-04-13 14:23:44 | BUILDING PLAN REVIEW |
| | PERMIT: 12120211 |
| | ADD: 424 PALM ST |
| | CONT: BENITZ BUILDING LLC |
| | TEL: (561)659-4024 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) COMPLIED. |
| | |
| | 1B)2ND REQUEST, IS THIS A CHANGE OF OCCUPANCY? THE |
| | PLANS APPEAR TO HAVE GONE FROM A WAREHOUSE AND AN |
| | ACCESSORY BUSINESS OCCUPANCY TO A MIXED USE MERCANTILE |
| | AND WAREHOUSE TYPE OCCUPANCY. THE DESIGNER REFERS TO |
| | INTERIOR DESIGN OFFICE BUT THE PLANS SHOW MORE THAN 50% |
| | OF THE FLOOR PLAN AS SHOW ROOMS AND A DISPLAY KITCHEN. |
| | THIS WOULD MAKE IT A MERCANTILE OCCUPANCY, ARE CLIENTS |
| | ALLOWED TO VIEW FURNATURE IN THE WAREHOUSE SUCH AS A |
| | COSTCO OR SAMS CLUB OR IS THIS AREA FOR EMPLOYEES ONLY. |
| | WHAT TYPE OF GOODS WILL BE STORED IN THE WAREHOUSE? |
| | WILL THIS AREA BE CONSIDERED A S1 OR S2 OCCUPANCY? |
| | DEPENDING ON THE TYPE OF STORAGE THERE MAY OR MAYNOT |
| | REQUIRE A FIRE RATING BETWEEN THE OCCUPANCIES PER 2010 |
| | FBC-B TABLE 508.4. |
| | |
| | 2010 EXISTING BUILDING CODE 901.3 CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 2) SHEET A2.1 THE ACCESSIBLE RESTROOMS: |
| | 2A-D) COMPLIED . |
| | |
| | 2E) COMPLIED. |
| | |
| | 3) SEE COMMENT 1B, SHEET A1.1 INDICATES THIS BUILDING |
| | AS A MIXED OCCUPANCY INTERIOR DESIGN OFFICE (BUSINESS) |
| | & STORAGE OCCUPANCIES THE PLANS JUST STATE WAREHOUSE |
| | NOT THE S1 OR S2 OCCUPANCY TYPE. |
| | DEPENDING ON THE TYPE OF MATERIALS STORAGED TABLE 508.4 |
| | MAY REQUIRE OCCUPANCY SEPERATION AND OPENING |
| | PROTECTIVES TABLE 715.4. |
| | |
| | 4) 2ND REQUEST, THIS DEPENDS ON THE ABOVE |
| | COMMENTRESPONCES.IN RATED FIRE RATED WALLS : 713.6 FIRE |
| | WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS |
| | AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| | PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| | IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| | AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| | SMOKE BARRIERS: ?FIRE AND SMOKE BARRIER ? PROTECT ALL |
| | OPENINGS.? |
| | |
| | 5) COMPLIED. |
| | |
| | 6) 2ND REQUEST. SHEET A5.1 INDICATES THE USE OF |
| | POLYICYNENE INSULATION UNDER THE ROOF SLAB SYSTEM AND |
| | NO IGNITION BARRIER. 2010 FBC-B 2603.4.1.6 REQUIRES A |
| | IGNITION BARRIER TO SEPERATE THE INSULATION FROM THE |
| | AREA ABOVE THE CEILING. A IGNITION BARRIER IS DIFFERENT |
| | FROM A THERMOBARRIER THAT IS REQUIRED UNDER 2603.4. |
| | PLEASE PROVIDE THE MANUFACTURERS TESTING, THEY DO HAVE |
| | A ES LEGACY REPORT NER-420. |
| | |
| | 7) 2ND REQUEST SHEET A5.1 DETAIL #4 IS MISSING THE BOND |
| | BREAK (SLIP SHEET) AS PER REQUIREMENT 2010 FBC-B |
| | 1402.2.1. |
| | RESPONCE INDICATES COMPLIANCE WITH ASTM D 226, THIS |
| | STANDARD DOES NOT DEAL WITH THE TWO LAYERS OF WHATEVER |
| | MATERIAL THAT IS BEING SPECED OUT, ONE THE STUCCO GRABS |
| | THE FIRST LAYER OF FELT IN THIS CASE IT WILL NOT MOVE, |
| | THE REQUIRED SECOND LAYER IS THE BOND BREAK THAT ALLOWS |
| | FOR MOVEMENT OF THE UNDER LAYER THE BOND BREAK, NEW TO |
| | THE 2007 FBC. |
| | |
| | 8) COMPLIED. |
| | |
| | 9)2ND REQUEST, PLEASE STAMP THE PRODUCT APPROVALS WITH |
| | A SHOP DRAWING TYPE STAMP THAT THE DESIGN PROFESSIONAL |
| | HAS REVIEWED THE APPROVAL AND FOUND THEM MEETING THE |
| | WIND AND ASSOCIATED PRESSURES. |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. NEEDS TO BE REVIEWED BY |
| | THEDESIGNER OF RECORD. |
| | (B) WINDOWS, NEEDS TO BE REVIEWED BY THE DESIGNER OF |
| | RECORD. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, NO PRODUCT |
| | APPROVAL WAS SUBMITTED. |
| | (F) SKYLIGHT, NO PRODUCT APPROVAL WAS SUBMITTED |
| | |
| | 11) SHEET A7.2 IN THE SAMPLE AND CONFERENCE ROOM IT |
| | APPEARS A NEW SKYLIGHT IS TO BE INSTALLED ALSO IN THE |
| | ENERGY CALCS BUT NO INFORMATION AS TO PRODUCT APPROVALS |
| | OR ROOF PRESSURES FOR THIS SKYLIGHT WERE PROVIDED OR |
| | ROOF FRAMING DETAILS. |
| | |
| | 12) 2ND REQUEST , THE MECHANICAL SHEET M2.1 DETAIL # 1 |
| | INDICATES THAT THE ROOF A/C STANDS ARE EXISTING, SHEET |
| | A1.1 INDICATES NEW A/C ROOF TOP EQUIPMENT NEXT TO THE |
| | NEW SKYLIGHT. IF THE COMPRESSORS ARE GOINGTO BE |
| | INSTALLED ON THE ROOF TOP AND PRE-ENGINEERED A/C STANDS |
| | ARE GOING TO BE INSTALLED RULE 9N-3 REQUIRES PRODUCT |
| | APPROVALS TO BE SUBMITTED. IF ROOF TOP PACKAGE UNITS |
| | ARE TO BE INSTALLED THEN STRUCTURAL PLANS WILL NEED |
| | DETAILS ON THE OPENING SIZES, REINFORCEMENT AND HOW THE |
| | ROOF TOP CURBS WILL BE FASTENED TO THE ROOF FRAMING. WE |
| | WILL ALSO NEED HOW THE ROOF TOP EQUIPMENT WILL BE |
| | FASTENED TO THE CURB. 1609.8. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |