| Plan Review Notes For Permit 12120211 |
| Permit Number |
12120211 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-17 15:26:09 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | PLUMBING DRAWINGS ARE OK | | | | | | 1. THE SHOWROOM RESTROOMS WILL BE REQUIRED TO BE A | | | MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR | | | SPACE FOR THE WATER CLOSET. (OTHER CONFIGURATIONS ARE | | | ALSO POSSIBLE). ALSO, PLEASE SEE BUILDING REVIEW NOTES | | | CONCERNING THE WAREHOUSE AND OFFICE RESTROOMS. | | | FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE | | | IS REQUIRED FOR WATER CLOSET FROM SIDE WALL. | | | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL | | | NOT BE PERMITTED IN THE 60" SPACE. | | | | | | 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15 | | | OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN OR EQUAL | | | (ALSO SEE EXCEPTION). | | | PLUMBING TABLE 403.1 (E) (F) | | | FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO | | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES | | | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING | | | FOUNTAINS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | |
|