Plan Review Notes
Plan Review Notes For Permit 12120211
Permit Number 12120211
Review Stop P
Sequence Number 1
Notes
Date Text
2012-12-17 15:26:09FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLUMBING DRAWINGS ARE OK
  
 1. THE SHOWROOM RESTROOMS WILL BE REQUIRED TO BE A
 MINIMUM OF 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR
 SPACE FOR THE WATER CLOSET. (OTHER CONFIGURATIONS ARE
 ALSO POSSIBLE). ALSO, PLEASE SEE BUILDING REVIEW NOTES
 CONCERNING THE WAREHOUSE AND OFFICE RESTROOMS.
 FBC ACCESSIBILITY CODE 2010 604.3.1 A 60" CLEAR SPACE
 IS REQUIRED FOR WATER CLOSET FROM SIDE WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
  
 2. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN OR EQUAL
 (ALSO SEE EXCEPTION).
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  