Plan Review Notes
Plan Review Notes For Permit 12120211
Permit Number 12120211
Review Stop M
Sequence Number 1
Notes
Date Text
2012-12-20 10:19:00*** CORRECTIONS NEED FOR MECHANICAL REVIEW ***
  
 1) SUBMIT AN UP TO DATE PRODUCT APPROVAL FOR THE A/C
 CONDENSER STANDS. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) PLAN M1.1, SHOW THE SIZE OF THE RETURN AIR FLEX DUCT
 GOING FROM THE OWNERS OFFICE & CONFERENCE ROOM TO AHU
 #5, SEE 2010 FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732