Plan Review Notes
Plan Review Notes For Permit 12120211
Permit Number 12120211
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-12-17 12:40:59424 PALM STREET
 PERMIT #12120211
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY (MERCANTILE) OF
 THE BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 INDICATE THE INTENDED USAGE OF THE OVEN LOCATED IN THE
 WARMING KITCHEN.
  
 THE EGRESS PLAN SHOWN ON DRAWING A2.1 DOES NOT COINCIDE
 WITH THE EXIT SIGNAGE PROVIDED ON E2.1.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  