| 2012-12-19 13:23:04 | BUILDING PLAN REVIEW |
| | PERMIT: 12120211 |
| | ADD: 424 PALM ST |
| | CONT: BENITZ BUILDING LLC |
| | TEL: (561)659-4024 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) THE COVER SHEET A1.1UNDER THE HEADING OF TYPE OF |
| | BUILDING LIST THIS BUILDING AS A TYPE VA, THE PLANS DO |
| | NOT PROVIDE ANY COMPLIANCE WITH THE 2010 FBC-B TABLE |
| | 601 FOR 1 HOUR RATING, TABLE 602 NOR TABLE 705.8. THIS |
| | BUILDING CAN BE A BUILDING TYPE VB WITH THE AREA |
| | FRONTAGE INCREASE TAKEN SEE 2010 FBC-B 506.2. |
| | |
| | 1B) IS THIS A CHANGE OF OCCUPANCY? 2010 EXISTING |
| | BUILDING CODE 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 2) SHEET A2.1 THE ACCESSIBLE RESTROOMS: |
| | 2A) 118 & 119 PLEASE REVIEW THE REQUIRED SIZE OF |
| | RESTROOMS UNDER THE 2010 FL ACCESSIBILITY CODE FIGURE |
| | 604.8.1.6 AND CODE SECTION 604.3.2 . |
| | 2B) RESTROOM WITH DOOR # 133 THE DOOR SWINGS IN OVER |
| | THE 60 INCH CLEAR FLOOR SPACE REQUIRED BY ACC CODE |
| | 604.3.2. |
| | 2C) RESTROOM WWITH DOOR # 133 PLEASE PROVIDE DETAILS |
| | FOR THE LOCATION OF WATER CLOSET INCOMPLIANCE WITH ACC |
| | CODE 604.2 WATER CLOSET LOCATION & GRAB BARS IN |
| | COMPLIANCE WITH 604.5. |
| | 2D) RESTROOM WITH DOOR # 133 PLEASE PROVIDE DETAILS FOR |
| | THE LAVATORY THAT SHOW COMPLIANCE WITH 606.1-5. |
| | 2E) SHEET A2.1 & A5.2 THE OFFICE RESTROOM IS ACTUALLY |
| | CONSIDERED A BATHROOM SINCE IT CONTAINS A SHOWER AND |
| | WOULD BE REQUIRED TO BE ACCESSIBLE. EVEN IF THIS WAS TO |
| | BE VIEWED AS 213.2 EXCEPTION # 4 THE 50 % RULE WAS NOT |
| | MET. 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET |
| | ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH |
| | 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING |
| | ROOM SHALL COMPLY WITH 603. |
| | |
| | 3) SHEET A1.1 INDICATES THIS BUILDING AS A MIXED |
| | OCCUPANCY MERCANTILE & STORAGE OCCUPANCIES THE PLANS |
| | JUST STATE WAREHOUSE NOT THE S1 OR S2 OCCUPANCY TYPE. |
| | DEPENDING ON THE TYPE OF MATERIALS STORAGED TABLE 508.4 |
| | MAY REQUIRE OCCUPANCY SEPERATION AND OPENING |
| | PROTECTIVES TABLE 715.4. |
| | |
| | 4) IN RATED FIRE RATED WALLS : 713.6 FIRE WALLS, FIRE |
| | BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE |
| | PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| | IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| | AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| | SMOKE BARRIERS: ?FIRE AND SMOKE BARRIER ? PROTECT ALL |
| | OPENINGS.? |
| | |
| | 5) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE WARMING |
| | KITCHEN, STUDIO 1 & STUDIO 2, WHAT ARE THESE AREAS |
| | GOING TO BE USED FOR? WILL THE KITCHEN BE USED FOR |
| | COOKING? |
| | 107.2.1 ADDITIONAL INFORMATION REQUIRED. 2010 |
| | ACCESSIBILITY CODE 606.1-5. |
| | |
| | 6) SHEET A5.1 INDICATES THE USE OF POLYICYNENE |
| | INSULATION UNDER THE ROOF SLAB SYSTEM AND NO IGNITION |
| | BARRIER. 2010 FBC-B 2603.4.1.6 REQUIRES A IGNITION |
| | BARRIER TO SEPERATE THE INSULATION FROM THE AREA ABOVE |
| | THE CEILING. |
| | |
| | 7) SHEET A5.1 DETAIL #4 IS MISSING THE BOND BREAK (SLIP |
| | SHEET) AS PER REQUIREMENT 2010 FBC-B 1402.2.1. |
| | |
| | 8) SHEET A5.1 & A2.1 BOTH INDICATE NEW PORTICOS, BUT |
| | THE PLANS FAIL TO PROVIDE ROOF DRAINAGE 2010 FBC-B |
| | 1503.4. |
| | |
| | 9) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. NEEDS TO BE REVIEWED BY |
| | THEDESIGNER OF RECORD. |
| | (B) WINDOWS, NEEDS TO BE REVIEWED BY THE DESIGNER OF |
| | RECORD. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, NO PRODUCT |
| | APPROVAL WAS SUBMITTED. |
| | (F) SKYLIGHT, NO PRODUCT APPROVAL WAS SUBMITTED |
| | |
| | 11) SHEET A7.2 IN THE SAMPLE AND CONFERENCE ROOM IT |
| | APPEARS A NEW SKYLIGHT IS TO BE INSTALLED ALSO IN THE |
| | ENERGY CALCS BUT NO INFORMATION AS TO PRODUCT APPROVALS |
| | OR ROOF PRESSURES FOR THIS SKYLIGHT WERE PROVIDED OR |
| | ROOF FRAMING DETAILS. |
| | |
| | 12) NOTE NO MECHANICAL PLANS WERE PART OF THIS |
| | SUBMITTAL IF THE COMPRESSORS ARE GOINGTO BE INSTALLED |
| | ON THE ROOF TOP AND PRE-ENGINEERED A/C STANDS ARE GOING |
| | TO BE INSTALLED RULE 9N-3 REQUIRES PRODUCT APPROVALS TO |
| | BE SUBMITTED. IF ROOF TOP PACKAGE UNITS ARE TO BE |
| | INSTALLED THEN STRUCTURAL PLANS WILL NEED DETAILS ON |
| | THE OPENING SIZES, REINFORCEMENT AND HOW THE ROOF TOP |
| | CURBS WILL BE FASTENED TO THE ROOF FRAMING. WE WILL |
| | ALSO NEED HOW THE ROOF TOP EQUIPMENT WILL BE FASTENED |
| | TO THE CURB. 1609.8. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |