2012-12-18 16:28:1012120148
 8130 N. JOG ROAD
 NEW GENERATOR TRANSFER SWITCH
  
 PLEASE REVISE/CLARIFY THE PLANS IN RESPONSE TO THE
 FOLLOWING REVIEW COMMENTS.
  
 EITHER A SERVICE RATED TRANSFER SWITCH WITH OVER
 CURRENT PROTECTION OR A SERVICE RATED MANUAL DISCONNECT
 WITH OVERCURRENT PROTECTION IS REQUIRED. NEC 230.66,
 225.36
  
 THE MAXIMUM OVER CURRENT PROTECTION ALLOWED FOR 3/0
 FEEDERS IS 200 AMPERES. NEC
 T 310.16
  
 PROVIDE A GROUNDING AND BONDING SYSTEM FOR THE DERIVED
 SYSTEM. VERIFY THE EXISTING SERVICE IS PROPERLY BONDED
 AND GROUNDED AT THE BUILDING. NEC 250.20
  