| Plan Review Notes For Permit 12120145 |
| Permit Number |
12120145 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-06 14:09:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLAN AND APPLICATION CONFLICT WITH THE SURVEY AND | | | AERIAL RECORDS. | | | | | | APPLICATION STATES THAT AN INSULATED ROOF IS TO BE | | | INSTALLED. ONE PLAN SHOWS AN EXISTING CONCRETE PATIO. | | | THE ENGINEERING SHOWS THAT A NEW INSULATED ROOF WILL BE | | | INSTALLED UNDER THE EXISTING ROOF, EXTENDING 3'10" FROM | | | EXISTING HOUSE. | | | | | | SURVEY SHOWS THIS AREA AS COVERED UNDER EXISTING ROOF. | | | AERIAL PHOTOGRAPHY VERIFIES THIS. | | | | | | REVISE SITE PLAN AND SURVEY TO CORRECTLY SHOW PROPOSED | | | CONSTRUCTION. | | | | | | 2. ALTHOUGH THE EXISTING STRUCTURE HAS BEEN REMOVED | | | FROM THE SPECIAL HAZARD FLOOD ZONE, THE AREA OF THE | | | PROPOSED IMPROVEMENT IS LOCATED IN THE SPECIAL HAZARD | | | FLOOD ZONE. AN ELEVATION CERTIFICATION, CONSTRUCTION | | | DRAWINGS, WHICH STATES PROPOSED ELEVATION IS REQUIRED. | | | PER 94-546(B), IMPROVEMENT IS TO BE 6" ABOVE THE BFE. | | | OTHERWISE, FLOOD VENTS ARE REQUIRED. | | | | | | |
|