| 2013-02-06 10:45:35 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE WINDOW AND DOOR PRESSURES ON SHEET A1.1 WERE NOT |
| | CHANGED TO REFLECT THE CHANGE IN EXPOSURE CATEGORY FROM |
| | B TO C FROM THE PREVIOUS REVIEW. PLEASE CORRECT. FBCR |
| | 301.2.1 |
| | |
| | 2) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CALCULATION FORMS. FBC ENERGY CONSERVATION |
| | 405.4.2 |
| | |
| | 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | STRUCTURAL MULLIONS OR PROVIDE SIGNED AND SEALED |
| | STRUCTURAL DETAILS FOR THEM. DCA RULE 9N-3 AND CITY |
| | AMENDMENTS 107.2.1.3 |
| | |
| | 4) THE MAXIMUM DESIGN PRESSURE FORM THE PRODUCT |
| | APPROVAL FOR THE 5 V CRIMP METAL ROOF OF -52.5 PSF IS |
| | TOO LOW FOR ROOF ZONES 2 AND 3. MEAN ROOF HEIGHT IS 20 |
| | FT, SLOPE IS 6/12 AND EXPOSURE IS C. PLEASE SUBMIT |
| | PRODUCT APPROVAL WITH HIGHER DESIGN PRESSURES. FBCR |
| | 301.1.1 |
| | |
| | 5) THE WINDOW SCHEDULE ON THE PLANS SPECIFIES DOUBLE |
| | HUNG WINDOWS AND THE PRODUCT APPROVALS THAT WERE |
| | SUBMITTED ARE FOR SINGLE HUNG WINDOWS. PLEASE CLARIFY |
| | AND CORRECT. DCA RULE 9N-3 |
| | |
| | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SOLID |
| | CORE FIBERGLASS EXTERIOR DOORS ( #S 2, 7 IN THE DOOR |
| | SCHEDULE) AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 7) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS HAS |
| | A MAXIMUM SIZE LIMIT OF 20.67 SQFT. THE 146" X 24" |
| | TRANSOM WINDOW (F) AT THE MASTER BEDROOM APPEARS TO |
| | EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL. |
| | PLEASE CORRECT. DCA RULE 9N-3 |
| | |
| | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 90 |
| | DEGREE CORNER CUSTOM EXTERIOR FOLDING DOORS. DCA RULE |
| | 9N-3 |
| | |
| | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | STORM PANELS ARE MISSING THE INSTALLATION INSTRUCTIONS |
| | REQUIRED BY DCA RULE 9N-3. A KEY PLAN AND AN |
| | INSTALLATION SCHEDULE IS ALSO REQUIRED. SEE SAMPLE |
| | INSTALLATION SCHEDULE AT HTTP://WPB.ORG/DEVELOPMENT/CON |
| | STRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF NOTE: ALL |
| | OF THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE LARGE |
| | MISSILE IMPACT RATED AND DO NOT REQUIRE SHUTTERS. |
| | |
| | 10) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 11) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE |
| | REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |