| 2012-12-19 10:31:45 | *** CORRECTIONS NEEDED FOR MECHANICAL REVIEW *** | | | | | | 1) SUBMIT ENERGY CALCULATIONS, SEE 2010 FBC/ENERGY | | | 401.2 & 405.4.2. | | | | | | 2) SUBMIT COOLING LOAD CAL'S., SEE 2010 FBC/ENERGY | | | 403.6.1. | | | | | | 3) SUBMIT DUCT DESIGN CAL'S. MANUAL D OR OTHER APPROVED | | | METHODS, SEE 2010 FBC/RES. M1601.1. | | | | | | 4) EQUIPMENT LISTING ON PLAN M1.0 SHOWS ALL THREE A/C | | | SYSTEMS AS UNIT #1, PLEASE CORRECT, PER 2010 CITY OF | | | WPB AMEND. 107.2.1 & 107.3.5.3 . | | | | | | 5) PLAN M1.0 SHOWS RETURN AIR GRILL NOT RETURNING TO | | | AHU #3, PLEASE CORRECT PER 2010 FBC/RES. M1602.4. | | | | | | 6) PLAN M1.0 SHOWS RETURN AIR GRILL RETURNING TO THE | | | SUPPLY SIDE OF AHU #2, PLEASE CORRECT PER 2010 FBC/RES. | | | M1602.4. | | | | | | 7) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | | RANGE/OVEN IN THE OUTDOOR BBQ SPACE. SEE 2010 FBC/RES. | | | M1901.1 & M1901.2. | | | | | | 8) SUBMIT COMBUSTION AIR CALCULATIONS AND MAKE UP AIR | | | FOR THE GAS CLOTHES DRYER, AND THE GAS WATER HEATER OR | | | PROVIDE FOR COMBUSTION AIR, SEE 2010 FBC/RES. G2407.1. | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|