Plan Review Notes
Plan Review Notes For Permit 12120131
Permit Number 12120131
Review Stop B
Sequence Number 1
Notes
Date Text
2012-12-19 16:37:012010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD HAZARD ZONE.
 THE LOWEST FINISHED FLOOR AND EQUIPMENT FOR THE
 STRUCTURE IS REQUIRED TO BE AT OR ABOVE 7'-6" BFE.
 SPECIFY THE PROPOSED ELEVATIONS ON THE PLANS. NOTE: THE
 ATTACHED GARAGE IS REQUIRED TO BE AT OR ABOVE THIS
 MINIMUM ELEVATION. CITY OF WEST PLAM BEACH MUNICIPLE
 CODES AND FBCR322
  
 2) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBCR401.3.
  
 3) SUBMIT TWO SETS OF A SIGNED AND SEALED SUB-SURFACE
 SOIL BEARING REPORT AS REQUIRED BY FBCR401.4
  
 4) THE EXPOSURE CATEGORY IS INCORRECTLY LISTED AS B.
 THE CORRECT EXPOSURE FOR THIS STRUCTURE IS C. FBCR
 301.2.1.4.3
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE NEW
 DWELLING AS REQUIRED BY FBC ENERGY CONSERVATION 401.2.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 WINDOWS, DOORS, ROOF COVERING, STORM PANELS, ETC. AS
 REQUIRED BY DCA RULE 9N-3 AND FBCR301.2.1.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 8) THE DESIGN INFORMATION ON SHEET C1 NEEDS TO BE
 UPDATED TO THE REFERENCED EDITION OF ASCE7, WHICH IS
 ASCE7-10. FBCR CHAPTER 43
  
 9) THE PROPOSED STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE THE CITY OF W.P.B. FLOOD ORDINANCE REQUIRES THE
 LOWEST FLOOR TO HAVE A MINIMUM ELEVATION OF 7'-6" ABOVE
 BFE. THE PLANS SHOW AN ELEVATION OF 8.0 MSL FOR THE
 DWELLING NOT BFE AND THE PLANS SHOW THREE 8" STEPS DOWN
 INTO THE GARAGE. THE GARAGE FLOOR AND EQUIPMENT ARE
 REQUIRED TO COMPLY WITH THE MINIMUM ELEVATION
 REQUIREMENT. FBCR322.1.4
  
 10) ON SHEET A3.0 ICYNENE SPRAY FOAM INSULATION IS
 SPECIFIED AS WELL AS ATTIC VENTS. WHEN THE FOAM
 INSULATION IS APPLIED TO THE UNDERSIDE OF THE ROOF
 SHEATHING, THIS TYPE OF ATTIC IS REQUIRED TO BE
 UNVENTED. PLEASE CORRECT. FBCR806.4
  
 11) SUBMIT TWO COPIES OF THE PRODUCT EVALUATIONS FOR
 THE SPRAY FOAM INSULATION. FBCR316.3
  
 12) PROVIDE FOOTING DETAILS FOR THE PADS AT THE C4 (4 X
 4 WOOD) COLUMNS. FBCR401.2
  
 13) PROVIDE DETAILS FOR THE INTERIOR BEARING WALL
 FOOTINGS AT THE GARAGE. FBCR401.2
  
 14) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING
 AS REQUIRED BY FBCR 803.2.3.1.
  
 15) PLEASE UPDATE THE WIND SPEED DATA ON SHEET S2.1 TO
 EXPOSURE C, 170 MPH FBC. FBC R301.2.1
  
 16) ON SHEET S2.0 SPECIFY THE TRUSS ANCHOR TYPES AND
 LOCATIONS. R802.1.6.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]