Plan Review Notes
Plan Review Notes For Permit 12120095
Permit Number 12120095
Review Stop M
Sequence Number 1
Notes
Date Text
2013-01-07 09:37:24*** PROVISO ***
  
 1) MUFFLER EXHAUST PIPE MUST TERMINATE 10 FT. FROM
 LOUVERED DAMPER, PER 2010 FBC/M 501.2.1 LOCATION OF
 EXHAUST OUTLETS. THE TERMINATION POINT OF EXHAUST
 OUTLETS AND DUCTS DISCHARGING TO THE OUTDOORS SHALL BE
 LOCATED WITH THE FOLLOWING MINIMUM DISTANCES:
 (2) FOR OTHER PRODUCT-CONVEYING OUTLETS: 10 FEET (3048
 MM) FROM THE PROPERTY LINES; 3 FEET (914 MM) FROM
 EXTERIOR WALLS AND ROOFS; 10 FEET (3048 MM) FROM
 OPERABLE OPENINGS INTO BUILDINGS; 10 FEET (3048 MM)
 ABOVE ADJOINING GRADE.
  
 2) PROVIDE REQUIRED PRODUCT APPROVAL FOR LOUVERED
 DAMPERS AS REQUESTED IN BUILDING REVIEW.
  