| 2013-01-07 09:37:24 | *** PROVISO *** | | | | | | 1) MUFFLER EXHAUST PIPE MUST TERMINATE 10 FT. FROM | | | LOUVERED DAMPER, PER 2010 FBC/M 501.2.1 LOCATION OF | | | EXHAUST OUTLETS. THE TERMINATION POINT OF EXHAUST | | | OUTLETS AND DUCTS DISCHARGING TO THE OUTDOORS SHALL BE | | | LOCATED WITH THE FOLLOWING MINIMUM DISTANCES: | | | (2) FOR OTHER PRODUCT-CONVEYING OUTLETS: 10 FEET (3048 | | | MM) FROM THE PROPERTY LINES; 3 FEET (914 MM) FROM | | | EXTERIOR WALLS AND ROOFS; 10 FEET (3048 MM) FROM | | | OPERABLE OPENINGS INTO BUILDINGS; 10 FEET (3048 MM) | | | ABOVE ADJOINING GRADE. | | | | | | 2) PROVIDE REQUIRED PRODUCT APPROVAL FOR LOUVERED | | | DAMPERS AS REQUESTED IN BUILDING REVIEW. | | | | | | MECHANICAL PLAN REVIEW BY: | | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|