2012-12-05 08:21:512010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C WITH
 A WIND SPEED OF 170 MPH VULT UPLIFT / 132 MPH VASD. THE
 COMPONENT AND CLADDING UPLIFT PRESSURES FOR THE
 PERIMETER AND CORNER AREAS EXCEED THE MAXIMUM DESIGN
 PRESSURE OF -52.5 PSF FOR THE PROPOSED ROOF SYSTEM ON
 PAGE 18 OF THE NOA USING JM ULTRAFAST SCREWS AND 3"
 PLATES. LIMITATION #7 ON PAGE 20 ALLOWS FOR INCREASED
 FASTENER DENSITIES IN THESE AREAS TO MEET THE ENHANCED
 UPLIFT PRESSURES. SIGNED AND SEALED RAS 117
 CALCULATIONS FROM A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT IS REQUIRED. FBCR301.2.1
  