| 2012-12-26 13:58:23 | | | | 12120056 | | | 4011 BROADWAY | | | INTERIOR RENOVATION TO BATHROOM | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENT. | | | | | | PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE EXISTING | | | SERVICE SIZE. SHOW CONDUIT AND FEEDERS TO THE RELOCATED | | | PANEL BOARD. INDICATE SIZE OF PANEL BOARD AND LOCATION | | | OF MAIN DISCONNECT. NEC 215.5 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | | | | |
|