| Plan Review Notes For Permit 12120052 |
| Permit Number |
12120052 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-16 12:15:09 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE MORE INFORMATION REGARDING EXISTING | | | CONDITIONS (TYPE OF WINDOW) FOR BEDROOM #2, FBC R310, | | | FBC EB 604.1. | | | | | | 2. OK | | | | | | 3. FOR THE SIDING, DESIGN PRESSURES FOR THE PRODUCT | | | (-30 AND -35PSF) ARE TOO LOW. ZONE 5, 10SF, EXPOSURE C, | | | 15 MRH, DESIGN PRESSURE REQUIREMENT IS +37.9/-50.7. | | | | | | 2ND REVIEW, PRODUCT APPROVAL SUBMITTED HAS A RANGE OF | | | DESIGN PRESSURE RATINGS DEPENDING ON PRODUCT, BUT THE | | | RANGE IS STILL TOO LOW (-40 PSF TO -47 PSF). | | | | | | | | | | | | | | 2013-01-07 16:29:08 | GAVE TO SAMANTHA |
|