| Plan Review Notes For Permit 12120052 |
| Permit Number |
12120052 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-11 18:57:40 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 2. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR AND | | | MATERIALS FBC 107. PROVIDE A COPY OF THE CONTRACT FOR | | | THIS JOB. PROVIDE OVERALL DIMENSIONS FOR THE STRUCTURE. | | | | | | 3. FOR THE SIDING, DESIGN PRESSURES FOR THE PRODUCT | | | (-30 AND -35PSF) ARE TOO LOW. ZONE 5, 10SF, EXPOSURE C, | | | 15 MRH, DESIGN PRESSURE REQUIREMENT IS +37.9/-50.7. | | | | | | | | | | | | |
|