| 2012-12-18 10:08:24 | BUILDING PLAN REVIEW |
| | PERMIT: 12110781 |
| | ADD: 105 EVERNIA ST |
| | CONT: CIRCUS AMERICA, INC |
| | TEL: (941)552-9952 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) THIS OCCUPANCY IS CONSIDERED AN A-2 OCCUPANCY, |
| | DINING, DRINKING, ENTERTAINMENT & DANCING. THE PLANS |
| | ARE DEFICIENT IN PROVIDING A LIFE SAFETY PLAN |
| | PROVIDING: |
| | 2010 FBC-B CHAPTER 1 / WEST PALM BEACH ADMINISTRATIVE |
| | CODE 107.3.5.1.1 |
| | (6) OCCUPANT LOAD & EGRESS CAPACITIES |
| | |
| | (7) . OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | |
| | STAIRS CONSTRUCTION/ RAMPS/ GEOMETRY AND PROTECTION |
| | PLANS ARE NOT DIMINSIONED FOR HEIGHT (S-4) |
| | 1003.5 ELEVATION CHANGE. |
| | WHERE CHANGES IN ELEVATION OF LESS THAN 12 INCHES (305 |
| | MM) EXIST IN THE MEANS OF EGRESS, SLOPED SURFACES SHALL |
| | BE USED. WHERE THE SLOPE IS GREATER THAN ONE UNIT |
| | VERTICAL IN 20 UNITS HORIZONTAL (5-PERCENT SLOPE), |
| | RAMPS COMPLYING WITH SECTION 1010 SHALL BE USED. WHERE |
| | THE DIFFERENCE IN ELEVATION IS 6 INCHES (152 MM) OR |
| | LESS, THE RAMP SHALL BE EQUIPPED WITH EITHER HANDRAILS |
| | OR FLOOR FINISH MATERIALS THAT CONTRAST WITH ADJACENT |
| | FLOOR FINISH MATERIALS. |
| | |
| | RAMPS IN COMPLIANCE WITH 2010 ACCESSIBILITY 405 (1-10). |
| | |
| | STAIRS 2010 FBC-B 1009 (1-4) |
| | |
| | GAURDS 2010 FBC-B 1013 (1-3) POSSIBLY IF IF STAGE IS |
| | OVER 30" IN THE VERTICAL DIMENSION. |
| | |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS 1017.4 (1-3) |
| | |
| | 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE |
| | DESIGN LOADS FOR THE , STAGE, STAIRS AND RAMPS |
| | |
| | (10.) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | VERTICAL ACCESSIBILITY 221.1.1 ACCESSIBILITY CODE |
| | 201.3 TEMPORARY AND PERMANENT STRUCTURES. |
| | THESE REQUIREMENTS SHALL APPLY TO TEMPORARY AND |
| | PERMANENT BUILDINGS AND FACILITIES. |
| | |
| | ADVISORY 201.3 TEMPORARY AND PERMANENT STRUCTURES. |
| | TEMPORARY BUILDINGS OR FACILITIES COVERED BY THESE |
| | REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO, REVIEWING |
| | STANDS, TEMPORARY CLASSROOMS, BLEACHER AREAS, STAGES, |
| | PLATFORMS AND DAISES, FIXED FURNITURE SYSTEMS, WALL |
| | SYSTEMS, AND EXHIBIT AREAS, TEMPORARY BANKING |
| | FACILITIES, AND TEMPORARY HEALTH SCREENING FACILITIES. |
| | STRUCTURES AND EQUIPMENT DIRECTLY ASSOCIATED WITH THE |
| | ACTUAL PROCESSES OF CONSTRUCTION ARE NOT REQUIRED TO BE |
| | ACCESSIBLE AS PERMITTED IN 203.2. |
| | |
| | 201.1.1 VERTICAL ACCESSIBILITY. |
| | SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS |
| | FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY |
| | |
| | TOILET FACILITIES |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |