| 2012-12-03 11:41:32 | 105 EVERNIA STREET |
| | PERMIT #12110781 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE EVENT VALUE ($1,000) APPEARS TO BE UNDERVALUED. |
| | VALUE SHALL INCLUDE BOTH LABOR AND MATERIALS. |
| | |
| | NO INFORMATION HAS BEEN PROVIDED ON THE COOK TENT. |
| | COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN |
| | VAPORS SHALL BE PROTECTED IN ACCORDANCE WITH NFPA 96 |
| | (KITCHEN EXHAUST HOOD AND AUTOMATIC SUPPRESSION |
| | SYSTEM). PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER |
| | AND ASSOCIATED SIGNAGE IN KITCHEN AREA. |
| | |
| | PROVIDE PLAN INDICATING EMERGENCY LIGHTING AND |
| | ILLUMINATED EXIT SIGNS. EMERGENCY ILLUMINATION SHALL BE |
| | PROVIDED FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF |
| | FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING |
| | FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL |
| | ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1 |
| | FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.1 |
| | FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR |
| | LEVEL. SEPARATE TEMPORARY ELECTRICAL PERMIT MAY BE |
| | REQUIRED. |
| | |
| | THERE APPEARS TO BE ONLY ONE EXIT FROM THE VIP LOUNGE |
| | TENT. NO SEATING OR FURNITURE LAYOUT HAS BEEN PROVIDED. |
| | PROVIDE PLAN INDICATING NORMAL LIGHTING, EMERGENCY |
| | LIGHTING AND ILLUMINATED EXIT SIGNS. |
| | |
| | THE PLAN DOES NOT INDICATE IF DOORS WILL BE INSTALLED |
| | AT THE EXITS. PANIC HARDWARE SHALL BE PROVIDED ON DOORS |
| | TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES |
| | ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| | HARDWARE. |
| | |
| | CURTAINS, DRAPES AND OTHER LOOSELY HANGING |
| | FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION |
| | CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH |
| | ONCE DIRECT FIRE FLAME HAS BEEN REMOVED). |
| | |
| | PLANS INDICATE THERE WILL BE A STAGE AND STAGE WITH |
| | DANCE FLOOR. PROVIDE ADDITIONAL INFORMATION SUCH AS |
| | STAGE CONSTRUCTION MATERIALS, ELEVATIONS, ADA ACCESS, |
| | ETC. |
| | |
| | POST WEATHERPROOF "NO SMOKING OR OPEN FLAME" SIGNS IN |
| | CONSPICUOUS LOCATIONS INSIDE AND OUTSIDE OF TENTS. |
| | |
| | INSPECTIONS ARE TO BE COORDINATED WITH THE BUREAU OF |
| | FIRE PREVENTION AT (561) 804-4724. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |