| 2012-12-04 08:51:19 | RESIDENTIAL (R3) DOOR REPLACEMENT BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- DOORS THAT HAVE GLAZING NEED TO PROVIDE OPENING | | | PROTECTION AS REQUIRED BY SEC. 606.4 OF 2010 | | | FBC-EXISTING BUILDING. ALL THE WINDOWS WHERE REPLACED | | | LAST YEAR AND IMPACT WINDOWS WHERE USED. SEE PERMIT | | | 11110254. SPECIFY HOW PROVIDING OPENING PROTECTION FOR | | | THE NEW DOORS. THERE ARE TWO OPTIONS. YOU CAN INSTALL | | | IMPACT WINDOWS OR INSTALL HURRICANE SHUTTERS. PROVIDE | | | PRODUCT APPROVAL FOR EITHER CHOICE AS REQUIRED BY DCA | | | RULE 9N-3. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE | | | IF USING HURRICANE SHUTTERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|