| Plan Review Notes For Permit 12110764 |
| Permit Number |
12110764 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-07 16:57:43 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PLANS INDICATE THAT THE EXISTING POOL SINGLE | | | MAIN DRAIN IS TO BE TIED IN WITH THE NEW SPA | | | CIRCULATION SYSTEM USING ONE 2 H.P. VARIABLE SPEED | | | JANDY STEALTH PRO SERIES PUMP. THIS MODIFICATION WILL | | | INCREASE THE WATER VELOCITY AT THE EXISTING POOL DRAIN | | | IN VIOLATION OF 2010 FBCR 4101.6.3 AND INCREASES THE | | | CHANCES OF ENTRAPMENT. PLEASE CORRECT. NOTE: THE | | | EXISTING BUILDING CODE ALLOWS THE EXISTING POOL | | | CIRCULATION SYSTEM TO REMAIN AS IT IS, AS LONG AS NO | | | CHANGES ARE MADE TO IT. THE NEW SPA IS REQUIRED TO | | | COMPLY WITH THE 2010 FBCR. | | | | | | 2) THE PUMP CURVE CHART THAT WAS SUBMITTED SHOWS A | | | TOTAL DYNAMIC HEAD OF 73 FEET. THIS IS A LOT OF HEAD | | | PRESSURE. SUBMIT THE TDH CALCULATIONS FROM THE ENGINEER | | | THAT WERE USED TO ARRIVE AT THIS NUMBER. INCLUDE THE | | | HEAD LOSS SPECS. FOR THE FILTER AND OTHER COMPONENTS. | | | CITY AMENDMENTS 107.2.1.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|