| Plan Review Notes For Permit 12110743 |
| Permit Number |
12110743 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-04 10:25:42 | 2475 MERCER AVENUE - #201 | | | PERMIT #12110743 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | EACH FIRE-RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED | | | WITH SIGNS OR STENCILING READING FIRE/SMOKE | | | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT | | | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|