2012-12-06 11:11:06*** CORRETCIONS NEEDED FOR MECHANICAL PLANS ***
  
 1) PROVIDE A DETAIN SHOWING HOW MUA-1 UNIT IS TO BE
 SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION,
 ETC.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8.
 2) PROVIDE A DETAIN SHOWING HOW EXHAUST FANS ARE TO BE
 SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION,
 ETC.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8.
 3) PROVIDE A DETAIN SHOWING HOW THE DUCT STANDS ARE TO
 BE SECURED TO ROOF AND DUCTS, WITH TYPE OF ANCHORS,
 SIZE, LOCATION, ETC.. SEE 2010 FBC/M 301.12 AND 2010
 FBC 1609.8.
 4) PROVIDE A DETAIN SHOWING HOW ROOF CURBS ARE TO BE
 SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION,
 ECT.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8.
  
 MECHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.)