| Plan Review Notes For Permit 12110721 |
| Permit Number |
12110721 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-06 11:11:06 | *** CORRETCIONS NEEDED FOR MECHANICAL PLANS *** | | | | | | 1) PROVIDE A DETAIN SHOWING HOW MUA-1 UNIT IS TO BE | | | SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION, | | | ETC.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8. | | | 2) PROVIDE A DETAIN SHOWING HOW EXHAUST FANS ARE TO BE | | | SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION, | | | ETC.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8. | | | 3) PROVIDE A DETAIN SHOWING HOW THE DUCT STANDS ARE TO | | | BE SECURED TO ROOF AND DUCTS, WITH TYPE OF ANCHORS, | | | SIZE, LOCATION, ETC.. SEE 2010 FBC/M 301.12 AND 2010 | | | FBC 1609.8. | | | 4) PROVIDE A DETAIN SHOWING HOW ROOF CURBS ARE TO BE | | | SECURED TO ROOF WITH, TYPE OF ANCHORS, SIZE, LOCATION, | | | ECT.. SEE 2010 FBC/M 301.12 AND 2010 FBC 1609.8. | | | | | | MECHANICAL PLAN REVIEW BY TOM GORDON (HY-BYRD INC.) | | | FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|