| 2012-12-27 11:18:55 | *** PROVISO *** |
| | 1) SUBMIT AN UP TO DATE PRODUCT APPROVAL FOR THE NEW |
| | A/C CONDENSER STAND, FOR REVIEW BEFORE FINAL MECHANICAL |
| | INSPECTION. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| | RULE 9N-3 NOV. 1, 2010, (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (G) EXTERIOR COOLER, FREEZERS & |
| | "PER-ENGINEERED A/C STANDS". ALSO SEE 2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | 2) CONDENSATE WATER FROM AHU-1 CAN NOT DISCHARGE INTO |
| | THE CITY WASTEWATER, PER CITY OF ORDINANCES CITY OF WPB |
| | CH.90 ARTICLE III SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE. (A) GENERALLY. USERS SHALL |
| | NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN |
| | ACCORDANCE WITH THIS ARTICLE. (B) DISCHARGE |
| | PROHIBITIONS. NO USER SHALL DISCHARGE INTO THE WWF ANY |
| | WASTE OR WASTEWATER WHICH MAY CAUSE PASS THROUGH OR |
| | INTERFERE WITH THE OPERATION OR PERFORMANCE OF THE WWF. |
| | NO USER SHALL DISCHARGE INTO THE WWF OR ANY CONNECTED |
| | SYSTEM ANY WASTE OR WASTEWATER CONTAINING ANY OF THE |
| | FOLLOWING: (5) STORM-WATER, SURFACE WATER, GROUNDWATER, |
| | ARTESIAN WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, |
| | SWIMMING POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| | UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| | CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| | IN WRITING. SEE 2010 FBC/M 307.2.1. |
| | 3) OFFICE 12 MAY NEED A R/A Z-BOOT, SEE 2010 FBC/M |
| | 601.4. |