| 2012-12-04 16:02:26 | BUILDING PLAN REVIEW |
| | PERMIT: 12110638 |
| | ADD: 319 CLEMATIS ST # 502 |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561)694-1214 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DEC. 04/2012 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW SHEET A-1.0 THE NEW EXECUTIVE BATHROOM |
| | DOOR AND ENTRY DOOR THERE IS LESS THAN 4'-0" BETWEEN |
| | DOORS, PLEASE SEE 2010 FBC ACCESSIBLITY CODE |
| | 404.2.6 DOORS IN SERIES. |
| | |
| | 2) CONFERENCE ROOM # 02 THE TENANT SEPERATION WALL IS |
| | MISSING A FIRE DAMPER IN ACCORDANCE WITH FBC-B 716.5.4. |
| | IT ALSO APPEARS THAT THE RESTROOM AND BREAKROOM EXHAUST |
| | AT THE TENANT SEPERATION WALL IS MISSING A FIRE DAMPER. |
| | |