| Date |
Text |
| 2012-12-18 11:03:36 | ***RESUBMITTAL DONE PRIOR TO FIRST BUILDING REVIEW. |
| | THEREFORE, BUILDING COMMENTS REMAIN AS PER FIRST |
| | REVIEW: |
| | |
| | |
| | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. FBC R 314.3.1, SMOKE DETECTORS IN EXISTING DWELLING |
| | REQUIRED. |
| | |
| | 2. FBC 107.2.1, ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 3. INCLUDE WIND DESIGN CRITERIA ON THE PLAN, FBC R 301. |
| | |
| | 4. IT IS NOT CLEAR HOW THE WALLS WILL BE STRUCTURALLY |
| | CONTINUOUS AROUND THE POSTS. DESIGN IS TO BE IN |
| | ACCORDANCE WITH ONE OF THE METHODS IN FBC R 301.1. HOW |
| | WILL SILL PLATES AND TOP PLATES BE INSTALLED THROUGH |
| | THE EXISTING COLUMNS WHICH ARE ATTACHED TO SLAB BELOW |
| | AND ROOF ABOVE? UNDER WHAT WIND DESIGN CRITERIA WAS THE |
| | CARPORT CONSTRUCTED? THIS IS A PARTIALLY ENCLOSED |
| | STRUCTURE, YOU ARE NOW MAKING A PORTION AN ENCLOSED |
| | STRUCTURE, BUT NO INFORMATION REGARDING REINFORCEMENT |
| | OF EXISTING WAS PROVIDED. IT APPEARS THAT ENGINEERING |
| | MAY BE REQUIRED. ADDITIONAL DETAILS SHOWING HOW THE |
| | WOOD FRAME WALLS WILL BE INTEGRATED INTO THE EXISTING |
| | STEEL COLUMNS WILL BE REQUIRED. |
| | |
| | 5. SHOW ROOM DESIGNATION FOR THE ROOM FROM THE HOUSE TO |
| | THE PROPOSED STORAGE AREA, FBC R 310 (TO CONFIRM |
| | BEDROOM EMERGENCY ESCAPE AND RESCUE IS NOT BLOCKED). |
| | |
| | 6. FOR THE SHUTTER, COMPLETE THE SAMPLE INSTALLATION |
| | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE |
| | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, |
| | FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN |
| | THE LOBBY OR ON THE INTERNET AT |
| | |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 7. FLORIDA STATE OR LOCAL PRODUCT APPROVAL COVER SHEET |
| | REQUIRED FOR THE DOOR, FAC9N-3. ONLY THE EVALUATION |
| | REPORT WAS PROVIDED. |
| | |
| | |
| | |