2012-12-04 09:02:32BUILDING PLAN REVIEW
 PERMIT: 12110592
 ADD: 1401 FORUM WAY # 600
 CONT: T & M DEVELOPMENT
 TEL: (561)2121398
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE SEE FIRE & MECHANICAL REVIEWS FOR COMMENTS
 THAT PERTAIN TO THE BUILDING REVIEW. SHEET UNDER THE
 HEADING" THIS PROJECT SHALL COMPLY WITH",
 EXISTING FIRE SEPERATIONS AT ELEVATORS, STAIRS,
 BUILDING ELECTRICAL & MECHANICAL ROOMS, ARE NOT
 MODIFIED OR ALTERED IN ANY MANNER.
  
 SHEET A1 THE RECEPTION LOBBY (101) / ELEVATOR LOBBY
 INDICATES A WALL TAG TYPE P2 & P4. THESE WALLS ARE
 INDICATED AS NON-RATED WALLS. PLEASE REVIEW THE 2010
 FBC-B 708.14.1 ELEVATOR LOBBY AND THE 7 EXCEPTIONS. THE
 PLANS DO NOT INDICATE THE ELEVATOR SHAFT TO BE
 PRESSURIZED IN ACCORDANCE WITH 708.14.2 SEE EXCEPTION #
 6. IT APPEARS WITH THE PARTITION TYPE P2 & P4 BEING
 DEPICTED FROM FLOOR TO CONCRETE DECK ABOVE THEY ARE
 BEING BUILT AS EITHER 1 HOUR FIRE RATING OR A SMOKE
 PARTITION (EXCEPTION #5) WOULD NEED TO MEET THE
 REQUIREMENTS LISTED WITHIN THE EXCEPTION, THE
 MECHANICAL PLANS DO NOT INDICATE THE USE OF ANY FIRE
 DAMPERS IN THIS LOCATION.
 IF THE P-4 WALL IS GOING TO BE BUILT AS A FIRE
 PARTITION THEN THE TEMPERED GLASS WINDOW WILL ALSO NEED
 TO QUALIFY UNDER THE REQUIREMENTS OF OPENING
 PROTECTIVES SEE TABLE 715.5 FOR FIRE PARTITION AND
 REQUIRED 3/4 HR WINDOW ASSEMBLY RATING.
  
 2) THE PLANS LACK IN PROVIDING THE MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
  
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 HIGH RISE 907.2.13 FIRE ALARMS
  
 7. LIFE SAFETY PLAN, OCCUPANCY LOAD/EGRESS REQUIREMENTS
 SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
  
 107.3.5.1.2 ELECTRICAL
  
 4. EMERGENCY SYSTEMS LIGHTING
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved