| Plan Review Notes For Permit 12110590 |
| Permit Number |
12110590 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-01-28 16:55:56 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. OK | | | | | | 2. STUCCO OVER WOOD SHEATHING REQUIRES A BOND BREAK, | | | FBC RESIDENTIAL 703.6.3. | | | | | | 2ND REVIEW, NOT ADDRESSED. NOT CLEAR WHY APPLICATION IS | | | FOR WOOD SIDING, DETAIL IS FOR STUCCO. | | | | | | 3. ROOF PERMIT REQUIRED. THE ROOF SUBCONTRACTOR MAY | | | SUBMIT FOR PERMIT AFTER ISSUANCE OF THE RENOVATION | | | PERMIT BUT MUST OBTAIN SUB PERMIT PRIOR TO COMMENCEMENT | | | OF WORK. (ADVISORY ONLY) | | | | | | 4. FOR THE ROOF, PROVIDE THE FOLLOWING: | | | | | | ON THE NOA, INDICATE WHICH APPROVED ASSEMBLY IS | | | PROPOSED | | | SEE GENERAL LIMITATION #7, ENHANCE FASTENING FOR ZONES | | | 2 AND 3 TO BE SPECIFIED BY AN ARCHITECT, ENGINEER, OR | | | REGISTERED ROOF CONSULTANT | | | | | | 2ND REVIEW, NOT ADDRESSED. ROOF SCOPE WILL BE REMOVED | | | IF NOT ADDRESSED PRIOR TO ISSUANCE OF WINDOW PERMIT. | | | |
|