| 2012-11-27 12:59:38 | THE PLANS ARE UNCLEAR AS TO THE SCOPE OF ELECTRICAL | | | WORK PROPOSED. | | | | | | PROVIDE A RISER PLAN FOR THE NEW ELECTRIC SERVICE TO | | | THE TRAILERS. SHOW LOCATION AND SAFETY CLEARANCES FOR | | | ALL ELECTRICAL PANELS. INDICATE ON THE SITE PLAN THE | | | LOCATION OF THE ELECTRICAL FEEDERS WITH OVER CURRRENT | | | PROTECTION. INDICATE THE REQUIRED DEPTH OF THE FEEDERS. | | | PROVIDE AN ELECTRICAL PLAN FOR THE KITCHEN EQUIPMENT. | | | NEC 215.5 | | | | | | PLEASE CALL FOR CLARIFICATION OF THESE COMMENTS. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|