| Plan Review Notes For Permit 12110558 |
| Permit Number |
12110558 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-20 15:57:42 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED | | | WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL | | | SERVICE. NEC 110.26, 240.24 | | | PROVIDE A LOAD CALCULATION FOR THE MAIN SERVICE FEED. | | | NEC 220.40 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|