Plan Review Notes
Plan Review Notes For Permit 12110557
Permit Number 12110557
Review Stop B
Sequence Number 2
Notes
Date Text
2013-02-27 08:34:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST:
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 NO INFORMATION PROVIDED REGARDING EXISTING WINDOWS. 38"
 IS TOO SMALL FOR A SINGLE HUNG TO MEET EMERGENCY ESCAPE
 AND RESCUE OPENING REQUIREMENTS OF FBC R 310.
  
 IT IS NOT CLEAR WHAT THE DRAWING IN THE CENTER OF THE
 PLAN IS, PLEASE CLARIFY BY REVISING PLAN (EXISTING
 OPENING 16X35).
  
 ONLY ONE PRODUCT APPROVAL SUBMITTED, TWO SETS REQUIRED
 FOR PERMIT ISSUANCE FBC 107.
  
  