Plan Review Notes
Plan Review Notes For Permit 12110527
Permit Number 12110527
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-03-12 09:26:462821 PINEWOOD AVENUE
 PERMIT #12110527
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 A SMOKE DETECTOR IS REQUIRED ABOVE THE FIRE ALARM
 CONTROL PANEL.
  
 THE STORAGE ROOM (NOW SHOWN AS "3-4-5 AFTER SCHOOL
 CARE") HAS ONE HORN-STROBE DEVICE LOCATED IN THE
 CORNER. AN ADDITIONAL DEVICE WILL BE REQUIRED IN
 SOUTHWEST CORNER OF THE ROOM TO PROVIDE ADEQUATE
 NOTIFICATION.
  
 THE "2 YEAR OLD'S CLASSROOM" HAS ONE HORN-STROBE DEVICE
 LOCATED 36 FEET FROM THE NORTH WALL. AN ADDITIONAL
 DEVICE WILL BE NEEDED ON THE NORTH WALL TO PROVIDE
 ADEQUATE NOTIFICATION.
  
 THE KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO
 THE FIRE ALARM SYSTEM.
  
 A NEW MANUAL PULL STATION WILL NEED TO BE ADDED TO ANY
 EXTERIOR DOORS TO BE ADDED IN FUTURE PERMITS (SUCH AS
 #13030290).
  
 REPEAT COMMENT: INDICATE THE EDITION OF NFPA 72 TO
 WHICH THE FIRE ALARM SYSTEM WAS DESIGNED AND INSTALLED.
  
 REPEAT COMMENT: FOR IDENTIFICATION PURPOSES, ASSIGN A
 NUMBERS/LETTERS TO EACH FIRE ALARM DEVICE ON THE
 SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730