| Plan Review Notes For Permit 12110527 |
| Permit Number |
12110527 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-11-26 08:58:58 | 2821 PINEWOOD AVENUE | | | PERMIT #12110527 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE SUBMITTED FIRE ALARM PLANS ARE LACKING THE | | | FOLLOWING INFORMATION: RISER DIAGRAM, PRODUCT DATA | | | CUTSHEETS, BATTERY CALCULATIONS, VOLTAGE DROP | | | CALCULATIONS, WIRE SIZES. CIRCUIT STYLE, ETC. | | | | | | THE PLANS DO NOT INDICATE IF THIS IS A ZONE STYLE | | | SYSTEM OR ADDRESSABLE SYSTEM. | | | | | | INDICATE THE NFPA STANDARD (AND EDITION) TO WHICH THE | | | FIRE ALARM SYSTEM WAS DESIGNED AND INSTALLED. | | | | | | PROVIDE A SCALABLE FLOOR PLAN. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS | | | TO EACH FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | THE PLANS DO NOT INDICATE THE LOCATION OF THE EXISTING | | | FIRE ALARM CONTROL PANEL. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|