| Plan Review Notes For Permit 12110523 |
| Permit Number |
12110523 |
|
| Review Stop |
AD |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-20 17:49:37 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. NOTE | | | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE | | | FOR BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 2ND REVIEW, NOT ENTIRELY ADDRESSED; PLEASE REVISE FLOOR | | | PLAN TO NOTE EXISTING CONDITIONS (TYPE OF WINDOW), | | | CLEAR OPENING SIZE FOR BEDROOMS, PROPOSED CLEAR OPENING | | | SIZE FOR BEDROOMS. | | | | | | 2. MINIMUM CODE ENVELOPE EFFICIENCY LEVELS SHALL BE MET | | | FOR COMPONENTS BEING CHANGED PER FBC ENERGY | | | CONSERVATION 2010 TABLE 101.4.1, ALSO SEE SECTION 402. | | | | | | 2ND REVIEW, NOT ADDRESSED. | | | |
|