| 2012-12-20 15:28:45 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 3. IF THE PROPOSED PRODUCT DOES NOT MEET THE MINIMUM |
| | STC AND IIC RATINGS AND AN UNDERLAYMENT IS PROPOSED, |
| | PROVIDE SPEC SHEETS. UNDERLAYMENT IS REQUIRED TO COMPLY |
| | WITH FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 2ND REVIEW - PROVIDE A COPY OF TEST DATA FOR STC, IIC, |
| | AND FLAME SPREAD. THE "MEGASHEET" SUBMITTED DOES NOT |
| | STATE HOW THE DATA WAS OBTAINED. IT IS ALSO NOT CLEAR |
| | WHETHER THE "MEGASHEET" IS FOR THE ATTACHED CORK OR IF |
| | AN ADDITIONAL UNDERLAYMENT IS PROPOSED. |
| | |
| | |
| | |