| Plan Review Notes For Permit 12110517 |
| Permit Number |
12110517 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-12-03 10:10:58 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | | | | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. | | | | | | 3. IF THE PROPOSED PRODUCT DOES NOT MEET THE MINIMUM | | | STC AND IIC RATINGS AND AN UNDERLAYMENT IS PROPOSED, | | | PROVIDE SPEC SHEETS. UNDERLAYMENT IS REQUIRED TO COMPLY | | | WITH FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | | | | | | | | | | |
|